Room temperature, ventilation and lighting in Germany: what ASR A3.5, A3.6 and A3.4 require
Too cold, too stuffy, too dark: indoor climate and light are the most common complaints in offices and halls. Which temperatures, CO2 values and illuminance levels the German Technical Rules for Workplaces set and what employees can ask for.
Last updated on 9 min readAMS Go editorial team
Key points at a glance
- The Workplaces Ordinance (ArbStättV) requires a room temperature conducive to health, sufficient healthy breathing air and as much daylight as possible (Annex nos. 3.4 to 3.6); the Technical Rules for Workplaces ASR A3.5, A3.6 and A3.4 give concrete values.
- Room temperature: minimum values of 12 to 20 °C depending on the heaviness of work; 26 °C should not be exceeded, above 30 °C effective measures are mandatory, and above 35 °C the room is not suitable as a work room without special measures.
- Ventilation: below 1,000 ppm CO2 nothing further needs to be done, between 1,000 and 2,000 ppm airing is improved, above 2,000 ppm further measures are required. Guide value for intermittent airing: after 60 minutes in an office, after 20 minutes in a meeting room.
- Lighting: work rooms need as much daylight as possible and a view to the outside. Minimum illuminance ranges from 50 lux in corridors and 300 lux at many workshop workplaces to 500 lux at office workplaces.
- Anyone who complies with the ASR can assume that the ordinance is met. Employees can make suggestions and complain; they are not entitled to a specific measure or to time off because of heat.
Three rules for indoor climate and light
The Workplaces Ordinance (Arbeitsstättenverordnung, ArbStättV) sets protection goals, not figures: work rooms must have a room temperature conducive to health, there must be sufficient healthy breathing air, and the rooms should receive as much daylight as possible. The figures are in the Technical Rules for Workplaces (Technische Regeln für Arbeitsstätten, ASR):
Room temperature
Protection goal in the ArbStättVAnnex no. 3.5
Technical ruleASR A3.5 “Raumtemperatur”
StatusIssued June 2010, last amended March 2022
Ventilation
Protection goal in the ArbStättVAnnex no. 3.6
Technical ruleASR A3.6 “Lüftung”
StatusIssued January 2012, last amended May 2018
Lighting and view to the outside
Protection goal in the ArbStättVAnnex no. 3.4
Technical ruleASR A3.4 “Beleuchtung und Sichtverbindung”
StatusIssued May 2023
ASR A3.5 applies to work rooms, break rooms, on-call rooms, sanitary rooms, canteens and first-aid rooms. It contains no provisions for rooms with specific operational requirements for the indoor climate, such as cold stores. ASR A5.1 applies to outdoor workplaces.
Room temperature under ASR A3.5: minimum and maximum values
The yardstick is the air temperature, measured with a radiation-shielded thermometer at a height of 0.6 m for seated work and 1.1 m for standing work. There are minimum values at the lower end and a stepped model at the upper end:
at least 20 °C
What appliesLight work while sitting, such as office work
at least 19 °C
What appliesMedium-heavy work while sitting or light work while standing and walking
at least 17 °C
What appliesMedium-heavy work while standing and walking
at least 12 °C
What appliesHeavy work while standing and walking
at least 21 °C
What appliesBreak rooms, on-call rooms, sanitary rooms, canteens and first-aid rooms; in washrooms with showers the air temperature should be at least 24 °C
up to 26 °C
What appliesShould not be exceeded. If the sun heats the room above 26 °C, windows, skylights and glass walls must be fitted with suitable sun protection
above 26 °C
What appliesWith outdoor temperatures above 26 °C and sun protection in place, additional measures should be taken; suitable drinks should be provided
above 30 °C
What appliesEffective measures in line with the risk assessment must be taken, technical and organisational before personal ones; suitable drinks must be provided
above 35 °C
What appliesWithout technical, organisational or personal protective measures as for heat work, the room is not suitable as a work room for as long as the value is exceeded
- The minimum values must be maintained for the entire period of use, not only as the morning goes on.
- If the minimum values cannot be reached even when the technical options are exhausted, the order of priority is workplace-related technical measures such as radiant heating, organisational measures such as warm-up times and personal measures such as suitable clothing.
- Examples of measures in heat: keep sun protection closed after working hours too, air at night and early in the morning, run equipment only when needed, use flexitime, relax dress codes, use fans.
- A risk to health can exist even above 26 °C, for example with heavy physical work, burdensome protective clothing, or for young people, older people, pregnant women and breastfeeding mothers. An adapted risk assessment then decides on further measures.
Details on summer and winter are in the guides “Heat in the workplace” and “Cold at work”.
Ventilation under ASR A3.6: CO2 as the yardstick
Healthy breathing air generally corresponds to the quality of outdoor air. If the people present are the main cause of the load on the room air, the CO2 concentration is the recognised measure of air quality. ASR A3.6 assigns three ranges:
below 1,000 ppm
MeasuresNo further measures, provided the use of the room is not expected to cause a rise above 1,000 ppm
CO2 concentration 1,000 to 2,000 ppm
MeasuresReview and improve airing behaviour, draw up an airing plan and define responsibilities, take a ventilation measure such as increasing the outdoor air flow rate or air exchange
above 2,000 ppm
MeasuresFurther measures required, such as increased ventilation or fewer people in the room
- Measuring is not normally required. Only if there is a well-founded suspicion of excessive values is a measurement taken under normal conditions of use; the instantaneous value is assessed.
- Intermittent airing (Stoßlüftung) is a short, intensive exchange of air lasting about 3 to 10 minutes. Guide values: after 60 minutes in an office, after 20 minutes in a meeting room.
- Minimum duration of intermittent airing for orientation: 3 minutes in winter, 5 minutes in spring and autumn, up to 10 minutes in summer.
- Window ventilation is only sufficient if opening areas and room depth fit: for intermittent airing the ASR specifies 1.05 m² of opening area per 10 m² of floor area and a room depth of up to 2.5 times the clear room height for single-sided ventilation, and 0.60 m² and 5 times for cross ventilation.
- A ventilation and air-conditioning system is required if natural ventilation is not sufficient, for example because of the room dimensions, in rooms without openable windows, or if windows may not be opened long enough because of noise or for security reasons.
Humidity, draughts and ventilation systems
Besides substance loads, ASR A3.6 also deals with moisture and heat loads. Room air does not normally need to be humidified; if complaints arise, the risk assessment examines whether measures are needed. If, on the other hand, moisture arises from operations, these values must not be exceeded unless the nature of the business requires higher humidity:
Air temperature 20 °C
Maximum relative humidity80 %
Air temperature 22 °C
Maximum relative humidity70 %
Air temperature 24 °C
Maximum relative humidity62 %
Air temperature 26 °C
Maximum relative humidity55 %
- Draughts: there must be no unreasonable draught in occupied areas. At an air temperature of 20 °C, a turbulence intensity of 40 % and light work, this is usually the case as long as the mean air velocity is below 0.15 m/s.
- Ventilation and air-conditioning systems must be functional at all times; a fault must be indicated by an automatic warning device (Annex no. 3.6 ArbStättV).
- You define inspection and maintenance intervals in the risk assessment, taking the manufacturer's information into account. The records on commissioning, maintenance and inspections must be available.
- Deposits and contamination in the system that could lead to an immediate health hazard through the room air must be removed without delay.
- Exhaust air from sanitary rooms, smoking rooms and kitchens must not be used as supply air.
Lighting under ASR A3.4: daylight and minimum values in lux
Work rooms must receive as much daylight as possible and have a view to the outside. The ordinance itself names exceptions, for example for rooms where operational, production or structural reasons stand in the way, or for archives, storage rooms and ancillary rooms. Rooms set up by 3 December 2016 may continue to be operated without a view to the outside until they are substantially extended or converted. Under ASR A3.4, daylight is sufficient if a daylight factor of more than 2 % is achieved at the workplace (more than 4 % with roof lights) or the translucent area is at least one tenth of the floor area. For artificial lighting, Annex 3 of the ASR sets minimum values:
Circulation areas and corridors without vehicle traffic
Minimum illuminance50 lx
Colour rendering index Ra40
Circulation areas and corridors with vehicle traffic, loading ramps and loading areas
Minimum illuminance150 lx
Colour rendering index Ra40
Stairs, escalators, lifts and corridors in the area of steps and changes in level
Minimum illuminance100 lx
Colour rendering index Ra40
Storage rooms for uniform or large items
Minimum illuminance50 lx
Colour rendering index Ra60
Storage rooms with search tasks for non-uniform items
Minimum illuminance100 lx
Colour rendering index Ra60
Storage rooms with reading tasks
Minimum illuminance200 lx
Colour rendering index Ra60
Dispatch and packing areas
Minimum illuminance300 lx
Colour rendering index Ra60
Break rooms, canteens, tea kitchens, washrooms, toilets, changing rooms
Minimum illuminance200 lx
Colour rendering index Ra80
Office: filing, copying
Minimum illuminance300 lx
Colour rendering index Ra80
Office: writing, reading, data processing
Minimum illuminance500 lx
Colour rendering index Ra80
Technical drawing by hand
Minimum illuminance750 lx
Colour rendering index Ra80
Reception desk, counter
Minimum illuminance300 lx
Colour rendering index Ra80
Assembly work: rough / medium-fine / fine
Minimum illuminance200 / 300 / 500 lx
Colour rendering index Ra80
Welding
Minimum illuminance300 lx
Colour rendering index Ra60
Motor vehicle workshops and test centres
Minimum illuminance300 lx
Colour rendering index Ra80
Kitchens
Minimum illuminance500 lx
Colour rendering index Ra80
Sales area / checkout area
Minimum illuminance300 / 500 lx
Colour rendering index Ra80
First-aid rooms
Minimum illuminance500 lx
Colour rendering index Ra90
- Uniformity: at no point in the area of the workplace may illuminance fall below 0.6 times the mean illuminance.
- Surrounding area: for workplaces with 300 lx, a mean of at least 200 lx is needed in the surroundings; for workplaces with 500 lx or more, at least 300 lx.
- Glare and flicker: disturbing glare and reflections must be minimised; glare that can lead to accidents must be avoided. Flicker must lead neither to accident hazards nor to fatigue.
- It must be possible to regulate daylight at the workplace according to the activity, for example with blinds.
- Maintenance: lighting installations must be checked regularly; failed lamps and dirty luminaires are among the defects that must be remedied without delay. Windows and skylights are cleaned regularly.
- Safety lighting: where a failure of general lighting endangers employees, safety lighting of at least 15 lx is required, available within 0.5 seconds.
- Existing workplaces: if meeting the minimum values would involve obviously disproportionate expense, the employer assesses the workplaces individually and ensures protection in another way.
What employees can ask for
The duties under the Workplaces Ordinance fall on the employer. Employees are not entitled to a specific measure such as air conditioning, but they are entitled to have the employer assess the hazard and take effective measures. In practice this route has proved its worth:
- 1
Report the deficiency specifically
Employees may make suggestions to the employer on all matters of safety and health protection (Section 17 (1) ArbSchG). Measured values with date, time and room are helpful: temperature, CO2 value or illuminance.
- 2
Involve the specialists and the works council
The occupational safety specialist and the company doctor advise on indoor climate and lighting. The works council has a right of co-determination on company rules for health protection (Section 87 (1) no. 7 of the Works Constitution Act, BetrVG).
- 3
Adapt the risk assessment
The employer examines the report, defines measures in the order technical, organisational, personal, and checks their effectiveness.
- 4
Complaint to the authority
If, on the basis of concrete indications, the measures are not sufficient and the employer does not remedy a complaint, employees can contact the competent occupational safety authority. They must not suffer any disadvantage as a result (Section 17 (2) ArbSchG).
Checklist: checking indoor climate and lighting
- Room temperature, ventilation and lighting assessed in the risk assessment for all work, break and sanitary rooms
- Minimum temperatures reached at the start of work, also after weekends and company holidays
- Sun protection on windows, skylights and glass walls in place and working
- Action plan defined for days above 26, 30 and 35 °C, drinks organised
- Windows can be opened, airing plan in place for meeting rooms and multi-person rooms
- CO2 concentration measured and measures documented where there are complaints about stuffy air
- Ventilation and air-conditioning systems maintained and inspected at the defined intervals, records available, fault indication works
- Illuminance at workplaces, in corridors, on stairs and in storage areas spot-checked and compared with the minimum values
- Defective and flickering luminaires reported and replaced, luminaires and windows cleaned
- Glare from sun and luminaires checked at display screen workplaces, glare protection in place
- Lighting and ventilation reassessed after conversions, new furnishing or changed activities
Free templates for this guide
As PDF and Excel, free – to use in your own company.
Frequently asked questions
What is the maximum temperature allowed in an office?
The air temperature should not exceed 26 °C. If it gets warmer despite sun protection when outdoor temperatures are high, additional measures should be taken; above 30 °C effective measures are mandatory. Above 35 °C the room is not suitable as a work room for as long as the value is exceeded unless protective measures as for heat work are taken (ASR A3.5).
Which CO2 value is permissible in an office?
ASR A3.6 does not set a limit value in the strict sense but three ranges: below 1,000 ppm no further measures are needed, between 1,000 and 2,000 ppm airing must be reviewed and improved, and above 2,000 ppm further measures are required, such as increased ventilation or fewer people in the room.
How often do rooms have to be aired?
As needed. As guide values, ASR A3.6 recommends intermittent airing after 60 minutes in an office and after 20 minutes in a meeting room. About 3 minutes are enough in winter, 5 minutes in spring and autumn, and up to 10 minutes in summer.
How many lux does an office workplace need?
For writing, reading and data processing, ASR A3.4 sets a minimum of 500 lux, for filing and copying 300 lux and for archives 200 lux. In corridors without vehicle traffic 50 lux is sufficient; on stairs it is 100 lux.
Does every work room need a window?
In principle, yes: work rooms must receive as much daylight as possible and have a view to the outside (Annex no. 3.4 ArbStättV). The ordinance names exceptions, for example where operational, production or structural reasons stand in the way, for rooms where people stay only briefly such as archives and storage rooms, and it protects existing rooms that were set up by 3 December 2016.
This guide gives a general overview of German occupational safety law and does not replace legal advice. The regulations in force and the rules of the statutory accident insurance institutions are authoritative.
Organise occupational safety digitally
With the occupational safety software AMS Go you handle risk assessments, safety instructions, inspections and more in one system – mobile and with AI support.
Newsletter
Occupational safety, straight to your inbox
New templates, guides and changes to regulations – free from AMS Go. The newsletter is in German. You can unsubscribe at any time via the link in every email.
More guides
- Basics
German Workplace Ordinance: duties and technical rules (ASR) at a glance
7 minRead - Health
Heat in the workplace: room temperature under ASR A3.5 and what to do above 26 °C